Melsec-q, 9 dedicated instructions function, Operation at execution of cset instruction – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 250: Error

Advertising
background image

9 - 20 9 - 20

MELSEC-Q

9 DEDICATED INSTRUCTIONS

Function

(1) This function clears reception data in the OS area. It does not clear the user data

reception area in the buffer memory.

(2) If the CSET instruction is executed while the read request (X03/X0A) or reception

abnormal detection signal (X04/X0B) is turned on, the CSET instruction is kept

waiting until the signal is turned off.

(3) The status of the CSET instruction, whether it is being executed or completed

normally/abnormally, can be checked by the complete device (D2) specified by

the setting data.

(a) Complete device ((D2) + 0)

This device turns on at the End processing of the scan at which the CSET

instruction is completed and turns off at the next End processing.

(b) Complete device ((D2) + 1)

It turns on/off by the status at which the CSET instruction is completed.

• At normal completion: It is kept turned off and does not change.

• At abnormal completion: It turns on at the END processing of the scan at

which the CSET instruction is completed and

turns off at the next END processing.

[Operation at execution of CSET instruction]

Scan

Sequence program

Q series C24

At abnormal completion

End

processing

Scan

Scan

CSET instruction

Complete device

Complete device+1

Execution of instruction

Setting processing

End

processing

End

processing

Error

(1) If the dedicated instruction is abnormally completed, the error flag (SM0) turns on

and the error code is stored in SD0.

See the following manuals according to the error code, and check/take action

according to the error.

<Error code>

4FFF

H

or less

: QCPU User's Manual

(Hardware Design, Maintenance and Inspection)

7000

H

or more: Section 10.2 of the User's Manual (Basic)