4 input instruction, Melsec-q, 9 dedicated instructions 9.4 input instruction – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 238: Set data, Control data, Point

Advertising
background image

9 - 8 9 - 8

MELSEC-Q

9 DEDICATED INSTRUCTIONS

9.4 INPUT Instruction

This instruction receives data in any message format specified by the user using the

non procedure protocol.

Applicable device

Internal device

(System, user)

MELSECNET/H,

MELSECNET/10

Direct J \

Set

data

Bit

Word

File register

Bit

Word

Special module

U \G

Index register Zn

Constant Others

(S)

(D1)

(D2)

INPUT

(D2)

(S)

(D1)

G.INPUT

Un

Command

[Executing

condition]

[Instruction

code]

Set data

Description

Set by

Data type

Un

Start I/O signal of the module

(00 to FE: Top two-digit when I/O signals are expressed in 3-digit.)

User

BIN16 bit

(S)

Head number of the devices in which control data is stored.

User,

system

(D1)

Head number of the devices in which receive data is stored.

System

Device name

Set data

(D2)

Bit device number to be turned on at completion of execution.

System

Bit

The file register per local device and program cannot be used as the set data.

Control data

Device

Item

Set data

Setting range

Set by

3

(S) + 0

Receive channel

• Set receive channel

1: Channel 1 (CH1 side)

2: Channel 2 (CH2 side)

1, 2

User

(S) + 1

Reception result

• Reception result by an INPUT instruction are

stored.

0: Normal

Other than 0: Error code

1

System

(S) + 2

Receive data count

• Receive data count is stored.

2

0 or more

System

(S) + 3

Allowable number of

receive data

• Set the allowable number of words for received

data that can be stored in (D1).

1 or more

User

POINT

(1) The command of G.INPUT cannot be converted into pulse.

(2) G.INPUT should be executed while the read request of the input/output signal

is turned on.

Advertising