Melsec-q, 3 specifications point – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 60

Advertising
background image

3 - 10 3 - 10

MELSEC-Q

3 SPECIFICATIONS

POINT

(1) When the external device and the Q series C24 connected in n:1 and m:n configurations

When the send signal of each device is connected as shown below, if the "Output control input" is

turned ON at two or more devices, the relevant devices output (send) data at the same time.

For the external device to transfer data normally,

• "Output control input" must be turned ON only when sending data.

• "Output control input" must be turned OFF when not sending data.

SDA

SDB

RDA

RDB

Q series C24

SDA

SDB

RDA

RDB

Q series C24

Receive
data

Send data

SDA

SDB

RDA

RDB

Output control input

External device or converter

Receive
data

Send data

Output control input

Receive
data

Send data

Output control input

(2) When the Q series C24 is used, if operation of the two interfaces is linked (see Section 4.5.2 (2)), the

time to send one character becomes the Q series C24 H/W gate OFF time.

(The Q series C24 turns OFF the gate after the one-character send time.)