10.1.4 Reading the data communication status (Transmission sequence status)

This section explains how to read the current status of the data communication using

the MC protocol stored in the buffer memory.

When GX Configurator-SC is used, check the status using the "MC protocol monitor"

screen (see Section 8.6.4).

When a transmission problem occurs, read operation is executed to check the status

of the data communication using the MC protocol.

(1) Transmission sequence status storage area (address: 255

H

and 265

H

)

The status of data communication using the MC protocol is stored as a numerical

value in buffer memory addresses 255

H

and 265

H

.

b15

to

b0

0 to 9

0 to 9

Buffer memory address

265

H

(Information on the CH1 side)

(Information on the CH2 side)

255

H

The following shows the correspondence between the numerical values in the

transmission sequence status storage area and the data communication status.

"6" "1"..."6" is repeated afterward.

Values 7 to 9 are stored when "mode switching" or "initialization
of transmission sequence" is performed.

E
N

Q

S

tation

num

b

er

H

L

Request

to CPU

Response

from

CPU

ACK

or

NAK

Message wait

Request from an external device

External
device

Q series C24

Stored
value

1

0

3

4

5

6

2

REMARK

When the target interface is not set to use the MC protocol, "0" is stored in the

transmission sequence status storage area.

(2) Example of a program that reads from transmission sequence

status storage area

The following shows an example of a program that reads from the transmission

sequence status storage area.

(input/output signals X/Y00 to X/Y1F of the Q series C24)

Example of FROM instruction

b15

to

b0

0

4

D0

D1

The CH1 side is waiting to receive a command message,
and is using non procedure or bidirectional protocol.

CH2 is accessing the PLC CPU upon reception of a
command message.

Reads the status of data communication
on the CH1 side from address 255

H

.

Reads the status of data communication
on the CH2 side from address 265

H

.

Read command