Melsec-q, 4 settings and procedures prior to operation, Point – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 98: 2) the setting and data flow in linked operation

Advertising
background image

4 - 17 4 - 17

MELSEC-Q

4 SETTINGS AND PROCEDURES PRIOR TO OPERATION

(d) Station number setting (switch 5 (common for both CH1 and CH2 sides))

• This setting is for communication using the MC protocol.

• When several the Q series C24s are connected on the same line with

multidrop connection, set the station number designated in the data items

of the transmission frame in each external device to 0 to 31 (0

H

to 1F

H

).

This number designates which external device is to be communicated

with the Q series C24.

• Set the station number to 0 when the system configuration of the external

device and the PLC CPU is 1:1.

External device

Station 0

Station 1

Station 2

Station 31

Q series C24

POINT

If the communication of data with external device is to be started, check the

specifications of the functions to be used and then make the settings and connect

the cables.

Make the following switch settings from the GX Developer if there is to be no

communication (if the cables are not to be connected) at the interface.

• Communication protocol setting

: Set between 0

H

and 7

H

.

• Transmission setting, communication rate setting: Set all to OFF.

(2) The setting and data flow in linked operation

(a) Set the related switches as follows when two Q series C24 interfaces are in

linked operation.

Switch number

Settings

Setting value

Operation setting

b0 = OFF

Data bit setting

Transmission setting

:

Set each switch on both CH1 and CH2 sides to

the same specification.

Switch 1

Communication rate setting

Match the external device.

Switch 2

CH1 side

Communication protocol setting

8

Operation setting

b0 = ON

Data bit setting

Transmission setting

:

Set each switch on both CH1 and CH2 sides to

the same specification.

Switch 3

Communication rate setting

Match the external device.

Switch 4

CH2 side

Communication protocol setting

0 to 7

Switch 5

Station number setting

Set according to (d) of (1)

Advertising
This manual is related to the following products: