Melsec-q, 3 specifications – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 73

Advertising
background image

3 - 23 3 - 23

MELSEC-Q

3 SPECIFICATIONS

Address

Decimal (Hex)

Applicable

protocol

CH1

CH2

Application

Name

Initial

value

MC Non

Bi

Registration

allowed/not

allowed

Reference

section

Switch setting error and mode switching error status

0: No error

Other than 0: Switch setting error and mode switching error

515

(203

H

)

For confirmation

of switch setting

and mode

switching

CH1 Communication protocol setting No. (b0)

0: Normal 1: Error

CH1 Communication rate setting (b1)

0: Normal 1: Error

CH1 Setting change prohibit time mode switching (b3)

0: Normal 1: Error

CH2 Communication protocol setting No. (b4)

0: Normal 1: Error

CH2 Communication rate setting (b5)

0: Normal 1: Error

CH2 Setting change prohibit time mode switching (b7)

0: Normal 1: Disable

Setting station No. (b14)

0: Normal 1: Out of range

Linked operation setting (b15)

0: Normal 1: Error

0

R

Not allowed

Section 4.3

Section

4.5.2

Section

8.6.9

Number of registered user frames

516

(204

H

)

0

H

: No registration

1 or more: Number of registered frames

User frame registration status (for confirmation of registration No.)

0: No registration

1: Registered

517 to 541

(205

H

to 21D

H

)

Bit corresponding to registration No. is 0(ON)/1(OFF).

Registration No.3E8

H

(1000) : Address 205

H

(b0) to

Registration No. 4AF

H

(1199) : Address 211

H

(b7)

Section

8.6.9

542

(51E

H

)

For confirmation

of user frame

Number of registered default registration frames (for system)

Depends

on

registration

status

R

Not allowed

Section

8.6.9

Section

9.1.2 of

User's

Manual

(Application)

543

(51F

H

)

Use prohibited

System area

Flash ROM system parameters write result

544

(220

H

)

For confirmation

of flash ROM

write result

0 : Normal completion
Other than 1 (error code) : Abnormal completion

RW

Not allowed

Section

8.6.9

Modem function error code (error code when modem function is

being used)

545

(221

H

)

0 : Normal completion

Other than 1 (error code) : Abnormal completion

Modem function sequence status

546

(222

H

)

0: Idle
1: Waiting for initialization
2: Initializing modem
3: Waiting
4: Checking password
5: Communicating
6: Notification in progress

7: Modem disconnected
8: Callback Request reception waiting
9: Callback Modem disconnect waiting
10: Callback Delay time waiting
11: Callback Reconnecting
12: Callback Rechecking password

Number of data registration for connection

547

(223

H

)

0: No registration

1 or more: Number of registration

Data registration status for connection
(for confirmation of registration No.)

0: No registration

1: Registered

548 to 549

(224

H

to 225

H

)

Bit corresponding to registration No. is 0(ON)/1(OFF).

Registration No. BB8

H

(3000) : Address 224

H

(b0) to

Registration No. BD5

H

(3029) : Address 225

H

(b13)

Number of data registration for initialization

550

(226

H

)

For confirmation

of modem

function

0: No registration

1 or more: Number of registrations

0

R

Not allowed

Section

8.6.2

Chapter 3

of User's

Manual

(Application)

Advertising