Melsec-q, 3 specifications – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 69

Advertising
background image

3 - 19 3 - 19

MELSEC-Q

3 SPECIFICATIONS

Address

Decimal (Hex)

Applicable

protocol

CH1

CH2

Application

Name

Initial

value

MC Non

Bi

Registration

allowed/not

allowed

Reference

section

Communication error clear request for CH1 and to turn LED off

0: ON, No initialization request

1: OFF, Initialization requested

SD WAIT (b0)

C/N (b4)

SIO (b1))

NAK (b5)

PRO. (b2)

ACK. (b6)

P/S (b3)

NEU. (b7)

0

(0

H

)

For system (b8) to (b15)

Communication error clear request for CH2 and to turn LED off

0: ON, No initialization request

1: OFF, Initialization requested

SD WAIT (b0)

NAK (b5)

SIO (b1)

ACK. (b6)

PRO. (b2)

NEU. (b7)

P/S (b3)

CH2 ERR. (b14)

C/N (b4)

CH1 ERR. (b15)

1

(1

H

)

For LED and

communication

error clear

For system (b8) to (b13)

0

RW

Not allowed

Section

8.6.10

Section

10.1.1

Section

10.1.2

Register/read/delete instructions

2

(2

H

)

0: No request

2: Read request

1: Register request

3: Delete request

Frame No. direction

3

(3

H

)

0: No designation

Other than 0: Frame No.

Registration/read/delete result storage

4

(4

H

)

0: Normal completion

Other than 0: Abnormal completion

Number of data bytes registered designation

5

(5

H

)

0 : No designation

Other than 0: Number of data bytes registered (maximum 80 bytes)

User frame

6 to 45

(6

H

to 2D

H

)

For flash ROM

access

0 : No designation

Other than 0: Registered data (maximum 80 bytes)

0

RW

Not allowed

Section

8.4.1

Section

8.4.2

Section

8.4.11

Section

8.4.12

Modem connection channel designation

46

(2E

H

)

0: Non

1: CH1

2: CH2

Notification execution designation

47

(2F

H

)

0: Do not execute.

1: Execute.

0

Number of connection retries designation

48

(30

H

)

1 to 5: Number of retries

3

Connection retry interval designation

49

(31

H

)

90 to 300: Connection retry interval (unit: s)

180

Initialization/connection timeout designation

50

(32

H

)

1 to 60: Timeout (unit: s)

60

Number of initialization retries designation

51

(33

H

)

1 to 5: Number of retries

3

Data No. for initialization designation

52

(34

H

)

0

H

: Send initialization data designated by the

designated area of the user frame for

transmission.

7D0

H

to 801F: Data No. for initialization

7D0

H

Data No. for connection designation

53

(35

H

)

BB8

H

to 801F

H

: Data No. for connection

GX Developer connection designation

54

(36

H

)

0: Do not connect.

1: Connect.

0

No - communication interval time designation

55

(37

H

)

0 : Wait infinitely

1 to 120: No communication interval (Waiting time for line

disconnection) (unit: min.)

30

RS · CS control yes/no designation

56

(38

H

)

For designation

of modem

function-1

0: No control

1: Controlled

1

RW

Allowed

Section

8.4.2

Section

8.4.3

Section

8.4.4

Chapter 3

of User's

Manual

(Application)

57 to 143

(39

H

to 8F

H

)

Use prohibited

System area

Advertising