Symptom

Cause

Corrective action

MC

B

id

ir

e

ct

io

nal

No

n

procedure

• An error was generated

on the MELSECNET/ H,

MELSECNET/10.

• The local station CPU

on the MELSECNET/H,

MELSECNET/10

generated an error.

• Check the error contents from the state of SB

and SW related to the MELSECNET/H,

MELSECNET/10 with the GX Developer

monitor, etc. and perform the checks and take

the corrective action described in the

MELSECNET/H, MELSECNET/10 reference

manual.

• Module installation

address designation

during communications

with intelligent function

module is incorrect.

• Change the transmit message designation data.

• Stop the CPU and restart data communications.

• Communication error

signal "C/N" turned on.

• A command that cannot

be transmitted during

RUN (sequence

program, parameters,

etc.) was transmitted, or

"Disable write during

RUN" is set.

• Set the "Enable/disable write during RUN"

switch to "Enable" by command.

10.3.7 Troubleshooting when communication error "P/S" generates

Symptom

Cause

Corrective action

MC

B

id

ir

e

ct

io

nal

No

n

procedure

• Data does not match the

parity bit setting.

• Check the Q series C24 and external device

data format and match the settings.

• Sum check codes do not

match.

• Check if the sum check code transmitted from

the external device is correct. (Recalculate)

• Communication error

signal "P/S" turned on.

• When CH1 and CH2 are

used in the linked mode,

the cable is not

connected to one of the

interface.

• When using CH1 and CH2 independently, check

that the Q series C24 is not in the linked mode.

• When using CH1 and CH2 in the linked mode,

also connect the cable to both of the interfaces.

Note

• If the cable is not connected to one of the

interfaces when CH1 and CH2 are used in

the linked mode, noise may enter and the

data may be destroyed and "Data cannot be

decoded" or "Communications error cause"

may occur.