9.7 SPBUSY Instruction

This instruction reads the status of data transmission and reception executed with

dedicated instructions.

Applicable device

Internal device

(System, user)

MELSECNET/H,

MELSECNET/10

Direct J \

Set

data

Bit

Word

File register

Bit

Word

Special module

U \G

Index register Zn

Constant Others

(D)

SPBUSY

SPBUSY

(D)

(D)

GP.SPBUSY

G.SPBUSY

Un

Un

Command

Command

[Executing

condition]

[Instruction

code]

Set data

Description

Set by

Data type

Un

Start I/O signal of the module

(00 to FE: Top two-digit when I/O signals are expressed in 3-digit.)

User

BIN16 bit

Set data

(D)

Head number of devices in which the read communication status is

stored.

System

Device name

Function

(1) The function reads the execution status of a dedicated instruction directed to a

module designated by the start I/O signal, and stores it in the device designated

by (D) or later.

(2) The execution status is stored in (D) in the form of "1" at the corresponding bit

when the processing of each instruction is started, and "0" when the processing is

completed.

The processing of each instruction is completed when the completion flag of each

instruction is turned from on to off.

(D) + 0

b15

to

b4 b3b2b1 b0

Stores the execution status of ONDEMAND, OUTPUT, PRR, and BIDOUT instructions directed to channel 1.
Stores the execution status of INPUT and BIDIN instructions directed to channel 1.
Stores the execution status of ONDEMAND, OUTPUT, PRR, and BIDOUT instructions directed to channel 2.
Stores the execution status of INPUT and BIDIN instructions directed to channel 2.
Stores the execution status of GETE and PUTE instructions.

0

(Always stores "0".)

(D) + 1

(3) The SPBUSY instruction is executed for every scan while the read command is

ON, if the system is executing during ON. And, the instruction will be executed for

a single scan when the read command rises from OFF to ON, if the system is

starting up.