3 - 18 3 - 18

MELSEC-Q

3 SPECIFICATIONS

POINT

(1) Use the FROM/TO instructions or other applicable commands to access the

buffer memory shown in this section when a program for a QnA series serial

communication module is utilized for the Q series C24 (see Section 2 in

Appendix).

In QCPU, the access to the buffer memory of an intelligent function module is

executed with a dedicated instruction.

It is not necessary to access directly using the FROM/TO instructions or other

instructions from the sequence program, except when accessing the buffer

memory as shown in the programming on each function reference page.

(2) When a program for a QnA series serial communication module is utilized for

the Q series C24, it is recommended to replace the instructions with the

dedicated instructions shown on the corresponding function reference page of

each manual for the Q series C24.

(3) The following initial settings (changing the default values) for data

communication must be performed by a registration operation using GX

Configurator-SC or by executing the CSET instruction for the sequence

program.

1) Initial settings for communication using the MC protocol

• Setting the unit of data length sent by the on-demand function

Word/byte units designation (addresses 150 (96

H

), 310 (136

H

))

• Setting the buffer memory used by the on-demand function

Buffer memory head address designation (addresses 160 (A0

H

), 320

(140

H

))

Data length designation (addresses 161 (A1

H

), 321 (141

H

))

2) Initial settings for communication using the non procedure/bidirectional

protocols

• Setting the unit of data length to be sent and received

Word/byte units designation (addresses 150 (96

H

), 310 (136

H

))

• Setting the transmission area

Transmission buffer memory head address designation (addresses 162

(A2

H

), 322 (142

H

))

Transmission buffer memory length designation (addresses 163 (A3

H

),

323 (143

H

))

• Setting the reception area

Receive buffer memory head address designation (addresses 166

(A6

H

), 326 (146

H

))

Receive buffer memory length designation (addresses 167 (A7

H

), 327

(147

H

))

For more details on the registration operation by GX Configurator-SC, see

the explanation of the system settings of the corresponding protocol in

Sections 8.4.5 to 8.4.8.

For more details on the CSET instruction, see Section 16.4 of the User's