1 troubleshooting when "run" led is turned off, Melsec-q – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 280

Advertising
background image

10 - 29 10 - 29

MELSEC-Q

10 TROUBLESHOOTING

10.3.1 Troubleshooting when "RUN" LED is turned OFF

Symptom

Cause

Corrective action

MC

Bidi

rectio

nal

No

n

procedure

• A transmission setting

switch is set to an

unusable position.

• Set the switch by GX Developer correctly and

after writing to the CPU reset the CPU.

• PLC CPU error.

• Remove the cause of the CPU error and reset

the CPU.

Note

• During the Q series C24 and external device

loopback test, the minimum parameters file

must be written to the CPU beforehand.

• Power module 5 V

current capacity is

insufficient.

• Calculate the 5 V current drain of each installed

module. If the current capacity is insufficient,

check power module selection.

Note

• Whether or not the current capacity is

insufficient can be checked by disconnecting

the expansion base and installing only the Q

series C24 to the basic base.

• The Q series C24

"RUN" LED turned off.

• Extraneous noise

caused the Q series

C24 to abnormal

operation.

• Check if the shield wire is 2-point ground.

• When ground is used with other devices,

ground the Q series C24 independently.