Melsec-q, 10 troubleshooting – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 270

Advertising
background image

10 - 19 10 - 19

MELSEC-Q

10 TROUBLESHOOTING

Protocol

Error code

(Hexa-

decimal)

Error

Error Contents

Signal

name

Corrective action

MC

Non

Proce-

dure

Bidire-

ctional

7E6A

H

Monitoring device

read point range

error

Read point of monitoring device is out of range.

Correct the setting value of the

read point of the monitoring

device.

7E6B

H

7E6C

H

7E6D

H

CPU abnormal

monitoring setting

value error

Setting value (fixed value) of CPU abnormal

monitoring is out of range.

Correct the setting value (fixed

value) of the CPU abnormal

monitoring.

7E6E

H

System error

The OS of the Q series C24 detected some error.

(

1)

7E6F

H

Modem connection

error

Modem is connected to an incorrect channel.

Correct the C

H

to which

notification is sent.

7E70

H

CPU error

The communication with the CPU could not be

performed normally.

C/N

If there is an error in the CPU,

eliminate the error on the CPU

side and communicate again.

7E81

H

to

7E8E

H

7EC1

H

7EC2

H

System error

The OS of the Q series C24 detected some error.

(

1)

7EC3

H

Double send

request error

A send request was performed while another send

request was being processed.

Interlock (handshake) the send

requests.

7EC4

H

Transmission data

count error

Transmission/

receipt buffer

setting error

Data larger than the transmit buffer size was

transmitted.

Transmission/receipt buffer settings out of range.

Make the transmission data

count smaller than the transmit

buffer size.

Make the non procedure

protocol transmit buffer size

larger.

Designate the first address and

size of transmission/receipt

buffer in the free area range of

the user.

7EC5

H

Flash ROM access

error

Write to Flash ROM was requested when the setting

modification enable/disable switch in the GX

Developer was set to OFF.

When writing to Flash ROM, set

switch shown left of the given

interface to ON and restart the

Q series C24.

7EC6

H

Flash ROM access

error

There is an error in the Flash ROM read/write

request contents.

Check the read/write request

data and designate the correct

data.

7F00

H

System error

The OS of the Q series C24 detected some error.

(

1)

The next data was received before processing of the

previous data was completed.

Increase the transmission time

by performing handshake with
the external device, etc.

7F01

H

Buffer full error

Multiple requests was simultaneously issued for one

channel.

Perform handshake with the

request source external device.

7F02

H

to

7F06

H

System error

The OS of the Q series C24 detected some error.

(

1)

An ASCII code that cannot be converted to binary

code was received.

Check and correct the external

device transmit message and
restart data communications.

7F20

H

ASCII

BIN

conversion error

An odd number of bytes of data was received during

data communications using ASCII

BIN

conversion.

PRO

When communicating using

ASCII

BIN conversion,

always transmit the data in even
number bytes units.

There is an error in the command (frame) part.

7F21

H

Receive header

area error

An ASCII code that cannot be converted to binary

code was received.

PRO

Check and correct the external

device transmit message and
restart data communications.

7F22

H

Command error

A nonexistent command or device was designated.

The remote password length is wrong.

PRO

Check and correct the external

device transmit message and
restart data communications.

7F23

H

MC protocol

message error

There is no data (ETX, CR-LF, etc.) following the

character area, or designation was incorrect.

PRO

Check and correct the external

device transmit message and
restart data communications.

Advertising