10 TROUBLESHOOTING

(a) When a communication error occurs, take corrective action according to

Section 10.3.

(b) The initial status of the LED ON and communications error indicates the

status when the

Q series C24 starts up by turning on the power or resetting

the PLC CPU.

(c) Each of the communications error status, C/N to SIO, CH1 ERR. and CH2

ERR., turns on when an error occurs, and keeps its on-status even after the

communication returns to normal.

The PLC CPU can check the aforementioned LED ON status and

communications error status, and initialize any error information using

read/write to the buffer memory of the

Q series C24 and input/output signals.

Initialize the error information according to Section 10.1.2.

(d) NAK to NEU. (No. 6 to 8) turn on/off depending on the status.

(e) SD WAIT turns on when data cannot be sent to the external device by the

transmission control of the

Q series C24 (waiting for data transmission).

• When transmission cannot be started.

• When a transmission pause request is received during data transmission.

(DSR signal is off, reception by DC3)

SD WAIT turns off when transmission becomes possible and data

transmission is started/resumed.