Melsec-q – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 293

Advertising
background image

10 - 42 10 - 42

MELSEC-Q

10 TROUBLESHOOTING

10.3.15 Troubleshooting when data cannot be communicated with the ISDN sub-address

Circumstance

Cause

Corrective action

MC

Non

procedure

protocol

Bidirection

al protocol

• Sub-address is incorrect.

• Review the sub-address.

• Modem does not support ISDN sub-

address.

• Use modem that supports ISDN sub-

address.

• Data cannot be

communicated with ISDN

sub-address

• Sub-address is incorrectly partitioned.

• Review how to partition the sub-address

using the TA manual.

10.3.16 Troubleshooting when constant cycle transmission does not operate normally

Circumstance

Cause

Corrective action

MC

Non

procedure

protocol

Bidirection

al protocol

• The setting value of the constant cycle

transmission is incorrect.

• Review the constant cycle transmission

setting.

• Does not operate in the

cycle time designated in the

constant cycle transmission

setting

• The cycle time is affected by some causes.

• Remove the causes or designate the cycle

time anticipating the causes.

10.3.17 Troubleshooting when condition agreement transmission does not operate normally

Circumstance

Cause

Corrective action

MC

Non

procedure

protocol

Bidirection

al protocol

• The setting value of the condition

agreement transmission is incorrect.

• Review the condition agreement

transmission setting.

• Does not operate in the

cycle time designated in

condition agreement

transmission setting

• The cycle time is affected by some causes.

• Remove the causes or designate the cycle

time anticipating the causes.

10.3.18 Troubleshooting when data cannot be received by an interrupt program

Circumstance

Cause

Corrective action

MC

Non

procedure

protocol

Bidirection

al protocol

• Interrupt issuance was not designated.

• Designate interrupt issuance.

• Receiving by instruction other than

BUFRCVS.

• Use BUFRCVS instruction to receive

interrupt data.

• Cannot receive data with

the interrupt program

• "Parameter setting" - "PC system setting" -

or "Interrupt pointer setting" are not set on

the PLC CPU side, or the settings are

incorrect.

• Review "Parameter setting" - "PS system

setting" - "Interrupt pointer setting" on the

PLC CPU side

10.3.19 Troubleshooting when data cannot be written to Flash ROM

Circumstance

Cause

Corrective action

MC

Non

procedure

protocol

Bidirection

al protocol

• Flash ROM overwrite allow/prohibit was not

set to allow.

• Set Flash ROM overwrite allow/prohibit to

allow.

• Cannot write data to Flash

ROM

• Setting change was not set to allow in the

switch settings by GX Developer.

• Set setting change to allow in the switch

setting by GX Developer.

Advertising
This manual is related to the following products: