MELSEC-Q

4 SETTINGS AND PROCEDURES PRIOR TO OPERATION

4.4.1 Connecting the RS-232 interface (full-duplex communications)

The following shows the connection precautions and connection examples when using

the Q series C24 RS-232 interface for full-duplex communications.

(1) Connection precautions

(a) For further information about the following items, see the explanation in the

applicable section in the User's Manual (Application).

• Controlling the communication on the Q series C24 side by the external

device side using the CD signal of the RS-232 interface.

This is affected by the "RS-232 CD terminal check setting" in "CHn

transmission control and others system setting change" screen on GX

Configurator-SC.

• Performing half-duplex communication using specifications on the external

device side (an example of such a connection is shown in this section).

• Using modem functions.

(b) The connection cable FG signal and shield are connected as follows.

Connection on the Q series C24 side

Notes

Connection cable FG signal

Connect to the Q series C24 connector

housing

Connection cable shield

Connect to the external device FG terminal

or the Q series C24 connector housing

Do not short the communication cable FG

signal and the SG signal.

When the FG signal and the SG signal are

connected inside the external device, do not

connect the FG signal to the Q series C24.

(c) When normal data communication is not obtained due to external noise,

perform the wiring as follows:

1) Connect the FG terminals on the external device and the Q series C24

using the shield of the connection cable.

2) Signals other than SG should be connected with SG signals in the

twisted pair.

FG

RD

SD

DTR

DSR

SG

RD

SD

DTR

DSR

SG

To Connector
housing

Q series C24

Shield

(External device)

POINT

When using an RS-232 to RS-422 converter to connect the external device and the

Q series C24, use a converter that is compatible with the external device and PLC

CPU system configuration (1:1).