6 how to read the current operation status, Melsec-q, Remark – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 264: 1) operation mode status storage area

Advertising
background image

10 - 13 10 - 13

MELSEC-Q

10 TROUBLESHOOTING

10.1.6 How to read the current operation status

This section explains how to read the current operation status of the Q series C24.

When GX Configurator-SC is used, check the status in the "Transmission control and

others monitor/test" screen (see Section 8.6.3).

REMARK

• The status of the switch settings by GX Developer can be checked by performing

read operations as described in Section 10.1.5.

• Refer to Section 4.5 for the switch settings.

(1) Operation mode status storage area

The current operation status of the Q series C24 is stored into the following buffer

memory areas.

1) Station No. storage area (address: 24F

H

)

b0

(Station No.)

0 to 31

b15

Buffer memory address 24F

H

to

2) Communication protocol status storage area (addresses: 252

H

and 262

H

)

b0

Mode number currently operating

Buffer memory address 252

H

262

H

(Information on the CH2 side)

(Information on the CH1 side)

1 to 7

1 to 7

b15

to

3) Transmission status storage area (address : 253

H

, 263

H

)

b15 b14 b13 b12 b11 b10 b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

Communication rate setting

Buffer memory address 253

H

263

H

(Information on the CH2 side)

(Information on the CH1 side)

1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0 1/0

1/0

1/0

1/0

1/0

1/0

1/0

1/0

1/0

1/0

1/0

1/0

1/0

Operation setting

Data bit setting

Parity bit setting

Even/odd parity setting

Stop bit setting

Sum check code setting

Write during RUN setting

Setting modification allow/prohibit

0

0

0

0

0

0

0

0