Melsec-q, 10 troubleshooting – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 271

Advertising
background image

10 - 20 10 - 20

MELSEC-Q

10 TROUBLESHOOTING

Protocol

Error code

(Hexa-

decimal)

Error

Error Contents

Signal

name

Corrective action

MC

Non

Proce-

dure

Bidire-

ctional

7F24

H

Sum check error

The sum check calculated by the Q series C24 and

the received sum check are not the same.

P/S

Recheck the external device

sum check.

7F25

H

Data length error

The length of the received data exceeds the receive

area size.

CHn

ERR.

Correct the "data length" that is

transmitted from the external
device.

Change the "word/byte units"

set by the Q series C24 to byte
units.

Increase the receiving area of

the Q series C24.

7F26

H

Command error

Another command was received before an unlock

processing while the remote password is registered.

CHn

ERR.

Perform the communication

after the unlock processing is
normally completed.

7F30

H

System error

The OS of the Q series C24 detected some error.

(

1)

7F31

H

Simultaneous

transmission error

The Q series C24 and an external device started

transmitting simultaneously.

Process by agreement with the

external device.

When necessary, change the

simultaneous transmission data
valid/invalid designation setting
by GX Configurator-SC. (buffer
memory addresses 9B

H

/13B

H

)

7F32

H

System error

The OS of the Q series C24 detected some error.

(

1)

7F40

H

No reception watchdog timer (timer 0) time-out

occurred.

PRO

Check if data was dropped from

the receive data.

Check if DTR control, etc.

interrupted reception.

7F41

H

Response watchdog timer (timer 1) time-out

occurred.

Check the status of the

message transmission
destination and restart data
communications, as required.

7F42

H

Time-out error

Transmit watchdog timer (timer 2) time-out

occurred.

Check if DTR control, etc.

interrupted transmission.

7F50

H

to

7F54

H

7F60

H

to

7F66

H

System error

The OS of the Q series C24 detected some error.

(

1)

7F67

H

Overrun error

The Q series C24 received the next data before it

completed receive processing of the previous data.

SIO

Decrease the data transmission

rate and restart data
communications.

Check whether a temporary stop

has occurred in the station in
which the Q series C24 is
installed. (For the QCPU this can
be checked using special register
SD1005.) If a temporary stop has
occurred, remove its cause.

7F68

H

Framing error

Data does not match the stop bit setting.

A malfunction occurred in the network because the

power source of the partner station was on or off.

Noise occurs in the network.

When the multidrop was connected, data was

transmitted simultaneously by multiple devices.

SIO

Match the Q series C24 and

external device settings.

Clear the error information

according to the error

information initialization request

(YE/YF).

In addition, when

communicating data with the

non procedure protocol, execute

the INPUT instruction, and read

and discard the unnecessary

data.

Measure the noise.

When connecting the multidrop,

remove the interlock so that
data will not be transmitted
simultaneously by multiple
devices.