Melsec-q – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 255

Advertising
background image

10 - 4 10 - 4

MELSEC-Q

10 TROUBLESHOOTING

(3) Checking by GX Configurator-SC

Display the "Monitor/test others" screen.

For details on display screens, see Section 8.6.9 of the User's Manual (Basic).

(4) Description of LED ON status and communications error status

Related protocol

No.

Status

signal

name

Description

Description when ON

(when LED is turned on

(1))

Description when OFF

(when LED is turned off

(0))

Initial

state

MC

Non

procedure

protocol

Bidirection-

al protocol

1

SD WAIT

Transmission wait status

Waiting for data

transmission

Data transmission start

OFF

Overrun or framing

error occurred.

OFF

2

SIO

SIO error status

OS area is full.

Received data was

deleted.

Normal

OFF

3

PRO.

Communication protocol

error status

Error occurred.

Normal

OFF

4

P/S

Status of parity error or

sum check error

Error occurred.

Normal

OFF

5

C/N

Access status with the

PLC CPU

(

1

)

Normal

OFF

6

NAK

Abnormal completion

status

Abnormal completion

transmission

Normal completion

transmission

OFF

7

ACK.

Normal completion

status

Normal completion

transmission

Abnormal completion

transmission

OFF

8

NEU.

Neutral status

Waiting to receive

command

Neutral

Command reception

(

2

)

9

CH2. ERR

Error occurrence status

on CH2 side

OFF

10

CH1. ERR

Error occurrence status

on CH1 side

Switch setting error

Mode switching error

Transmission error

Reception error

On-demand error

Normal

OFF

1 C/N turns on in the following cases:

• An external device issued a data read request to the PLC CPU when write

during RUN is set to prohibit in the switch settings by GX Developer (see

Section 4.5.2).

For functions that cannot be used when write during RUN is set to prohibit, see

the explanation section in each command list of the Reference Manual.

• When an error has occurred during access between the Q series C24 and the

PLC CPU.

2 NEU. is valid when a target interface is set to use the MC protocol.

When the target interface is set to other than the MC protocol, the status of NEU.

is off.

Advertising