Melsec-q, 9 dedicated instructions function – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 236

Advertising
background image

9 - 6 9 - 6

MELSEC-Q

9 DEDICATED INSTRUCTIONS

Function

(1) Data stored in the device designated in (S2) and succeeding devices are sent

according to the control data of the device designated in (S1) and succeeding

devices, via the non procedure protocol of the module specified in Un.

b15

b0

to

(S2) + 0

+ 1
+ 2

Channel 1

Channel 2

QCPU

Q series C24

Send

Send

Channel to be
used is set by
the control data.

(2) The following instructions cannot be executed on a channel on which an OUTPUT

instruction is being executed.

• Other OUTPUT instructions

• PRR instructions

If an attempt is made during execution of an OUTPUT instruction to execute one

of the instructions above, the second instruction will not be executed until the

execution of the OUTPUT instruction is completed.

(3) Whether an OUTPUT instruction was completed normally or abnormally can be

checked by the completion device ((D)) or status display device at completion

((D)+1).

(a) Completion device: Turns on at the END processing of the scan where the

OUTPUT instruction is completed, and turns off at the

next END processing.

(b) Status display device

at completion

: Turns on and off depending on the completion status

of the OUTPUT instruction.

• Normal completion : Off with no change.

• Abnormal completion: Turns on at the END

processing of the scan where

the OUTPUT

instruction is

completed, and turns off at

the next END processing.

[Operation during execution of an OUTPUT instruction]

OUTPUT instruction

Execution of OUTPUT
instruction

Completion of transmission by
the OUTPUT instruction

ON

ON

OFF

OFF

END
processing

END
processing

END
processing

END
processing

Sequence
program

Completion device

Status display device
at completion

Abnormal
completion

Normal

completion

One scan

Advertising