[Setting Items]

The following table shows the selection menus for system setting/registration to

be displayed:

Function

Section

Remarks

User frame registration

Section 8.4.1

Data for modem initialization registration

Section 8.4.2

Data for modem connection registration

Section 8.4.3

Modem function system setting

Section 8.4.4

Transmission control and others system setting

Section 8.4.5

MC protocol system setting

Section 8.4.6

Non procedure system setting

Section 8.4.7

Bidirectional system setting

Section 8.4.8

PLC CPU monitoring system setting

Section 8.4.9

Transmission user frame No. designation system setting

Section 8.4.10

Can be used via online

operation.

Can be used via offline

operation.

Resetting buffer memory/flash ROM setting values to default values

Section 8.4.11

Flash ROM write allow/prohibit setting

Section 8.4.12

Can be used only via online

operation.

POINT

(1) The User's Manual (Basic) and GX Configurator-SC's Help function provide

the code list. Use this list as a reference.

(2) The values set in the respective setting screens explained in Section 8.4 can

be written to the Q series C24 module (via online operation only) or saved to a

file.

(3) Perform the following operations in advance to enable the registration of

setting values in the flash ROM:

(a) Switch setting using the GX Developer (see Section 4.5.2)

Set "Setting change" under [Transmission settings] to "Enable" for both

the CH1 and CH2 sides.

(b) Setting using GX Configurator-SC (see Section 8.4.12)

Set the flash ROM write allow/prohibit designation to "Allowed".

(4) Some system setting screens have a pair of screens: one for CH1 and the

other for CH2. Please note that the explanations given in Section 8.4.1 and

thereafter apply to the online operations performed in the CH1 screens.

The setting items are the same between CH1 and CH2, but different buffer

memory addresses are used to store the setting values. The respective

addresses are indicated as follows where applicable.

(Left side: address for the CH1 side, right side: address for the CH2 side)

Setting item

Setting value storage buffer

memory address

Reference section containing detailed

explanation

DTR/DC control

designation

93

H

/133

H

Chapter 7 of

User's Manual (Application)

(5) When a multiple CPU system is employed, GX Configurator-SC should be

connected to the control PLC of the Q series C24, and the system setting data

register in the flash ROM.

It is not possible to set target PLC to multiple CPU setting of "Transfer setup"

of GX Developer and register the system setting data in the flash ROM.