10 - 15 10 - 15

MELSEC-Q

10 TROUBLESHOOTING

10.2 Error Code Tables

The following shows the error codes, error contents, and corrective action for errors
that are generated during communication between the Q series C24 and an external
device.
The signal name in the following table indicates the CH side LED on status or
communication error status that is stored into buffer memory address 201

H

/202

H

when

an error occurs.
The CH side LED on status and communication error status can be confirmed by GX
Developer's System monitor or GX Configurator-SC. (Refer to Section 10.1.1.)
For errors without a corresponding signal name entered to errors generated with the
MC protocol communication, “NAK” comes on.

10.2.1 Error code table

The following shows the error codes, error contents, and corrective action for errors
generated during communication using MC protocol (excluding A compatible 1C
frame), non procedure protocol, and bidirectional protocol.
(" " in the table is the error code when the target CPU is not a Q/QnACPU.)

Protocol

Error code

(Hexa-

decimal)

Error

Error Contents

Signal
name

Corrective action

MC

Non

Proce-

dure

Bidire-
ctional

3E8

H

to

3FFF

H

(Error detected by the CPU)

See Troubleshooting of the

QCPU (Q mode) maintenance
and inspection user's manual
and take corrective action.

4000

H

to

4FFF

H

(Error detected by the CPU)

See Appendix of the QCPU (Q

mode) maintenance and
inspection user's manual
(details) and take corrective
action.

7101

H

7102

H

System error

The OS of the Q series C24 detected some error.

(

1)

7103

H

PLC access error

Cannot communicate with the Q series C24 CPU.

C/N

Make the watchdog timer (timer

1) time longer.

Check if the CPU can

communicate in communication
protocol No. "F".

7104

H

to

7116

H

System error

The OS of the Q series C24 detected some error.

(

1)

7140

H

Request data error

Number of request points exceeds the range for the

command.

A word device was designated in a bit units

command.

The last device No. exceeds the range.

Given device last No. > Designated head device
No. + Designated number of points

PRO

Check and correct the external

device transmit message and
restart data communications.

7141

H

System error

The OS of the Q series C24 detected some error.

(

1)

7142

H

Device name error

A device that cannot be designated by the given

command was designated.

PRO

Check and correct the external

device transmit message and
restart data communications.

7143

H

Device No. error

The head device No. is out of range.

PRO

Check and correct the external

device transmit message and
restart data communications.

7144

H

Monitor data write
error

Monitoring was requested before the device to be

monitored was written.

PRO

Write the device to be monitored

before issuing a monitor request.

7145

H

Monitor PLC No.
error

The written PLC No. and PLC No. in the monitor

request are different.

C/N

Rewrite the monitor data.

7146

H

Monitor CPU model
name error

The written CPU model name and the CPU monitor

name in the monitor request are different.

C/N

Rewrite the monitor data.

7147

H

Written number of
monitoring points
overrun error

The written number of monitoring points exceeds

the designated range.

PRO

Check and correct the external

device transmit message and
restart data communications.