Melsec-q, 9 dedicated instructions, Function – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 239

Advertising
background image

9 - 9 9 - 9

MELSEC-Q

9 DEDICATED INSTRUCTIONS

1 For error codes relating to abnormal completion, see Chapter 10 of the User's

Manual (Basic).

2 When setting "Word/byte units designation" by GX Configurator-SC, set the number

of bytes when bytes are designated and set the number of words when words are

designated.

3 The settings are done by either of the following:

• User: Data set by the user before executing the INPUT instructions.

• System: The PLC CPU stores the execution result of the INPUT instructions.

Function

(1) The function stores in the device designated in (D1) and succeeding devices the data

received with the non procedure protocol of the module designated in Un, according

to the control data of the device designated in (S) and succeeding devices.

(2) When an INPUT instruction is executed on a channel, other INPUT instructions

cannot be executed on the channel at the same time.

If an attempt is made during execution of an INPUT instruction to execute another

INPUT instruction, the second instruction will not be executed until the execution

of the first INPUT instruction is completed.

(3) In case of reading the receive data to the same interface, it cannot be used along

with BUFRCVS instruction (for interrupt programs).

(4) Whether an INPUT instruction was completed normally or abnormally can be

checked by the completion device ((D2)) or status display device at completion

((D2)+1).

(a) Completion device: Turns on at the END processing of the scan where the

INPUT instruction is completed, and turns off at the next

END processing.

(b) Status display device

at completion

: Turns on and off depending on the completion status

of the INPUT instruction.
• Normal completion : Off with no change.
• Abnormal completion: Turns on at the END

processing of the scan where
the INPUT instruction is
completed, and turns off at
the next END processing.

[Operation during execution of an INPUT instruction]

Execution of INPUT
instruction

Completion of reception by
an INPUT instruction

ON

ON

OFF

OFF

Sequence
program

INPUT
instruction

Completion device

Status display device
at completion

END
processing

END
processing

Abnormal
completion

Normal

completion

One scan

END
processing

END
processing

Advertising
This manual is related to the following products: