10 TROUBLESHOOTING

10.2.2 A compatible 1C frame communications error code table

The following table lists the error code, error contents, and corrective action for errors

generated during A compatible 1C frame communications.

Protocol

Error code

(Hexa-

decimal)

Error

Error Contents

Signal

name

Corrective action

MC

Non

Proce-

dure

Bidire-

ctional

00

H

Disable during

RUN

A write command was designated when "Disable

write during RUN" was set.

Parameter or sequence program was written during

RUN.

C/N

Change the setting to "Enable

write during RUN" and restart

data communications.

Stop the CPU and restart data

communications.

01

H

Parity error

The data does not match the parity bit setting.

P/S

Match the Q series C24 and

external device settings.

02

H

Sum check error

The sum check calculated by the Q series C24 and

the transmitted sum check are not the same.

P/S

Check the external device sum

check.

03

H

Protocol error

Received message that is different from the control

procedure with the communication protocol setting.

PRO

Check and correct the external

device transmit message and

restart data communications.

04

H

Framing error

The data does not match the stop bit setting.

SIO

Match the Q series C24 and

external device settings.

05

H

Overrun error

The next data was received before the Q series C24

received all the preceding data.

SIO

Decrease the transmission rate

and restart data communications.

06

H

Character area

error

Designation method error in part of a message.

A command that does not exist was designated.

The number of processing points is outside the

range for the command.

A device that does not exist was designated.

PRO

07

H

Character error

Received data that cannot be used.

PRO

Check and correct the external

device transmit message and

restart data transmission.

08

H

PLC access error

The CPU cannot communicate with the Q series

C24.

C/N

Replace the CPU with a CPU that

can communicate with the Q

series C24.

10

H

PLC No. error

The PLC No. is not "FF", or a station No. set in the

network parameters.

C/N

Check and correct the external

device transmit message and

restart data communications.

11

H

Mode error

An error was detected upon access to the PLC

CPU.

Send again.

Conduct individual station recovery

test and check the Q series C24.

12

H

Special function

module designation

error

A special function module does not exist at the

specified position.

C/N

Check and correct the external

device transmit message and

restart data communications.

21

H

Special function

module bus error

An error was detected upon access to a special

function module at the specified position.

C/N

Check the error and take

corrective action according to the

manual of the corresponding

module.

42

H

Other errors

See

POINT .

POINT

If an error occurs during A compatible 1C frame communications, the Q series C24

adds a 2-character error code (00

H

to 10

H

, 42

H

) to the "NAK" code and returns the

"NAK" code to the external device and stores the error code (equivalent to QnA

compatible 2C/3C/4C frame error code) to buffer memory address 25A

H

(CH1) or

26A

H

(CH2).

The exact error contents can be checked by reading the value stored to the

buffer memory.

See Section 10.2.1 for a detailed description of the error codes.