2 - 11 2 - 11

MELSEC-Q

2 SYSTEM CONFIGURATION AND AVAILABLE FUNCTIONS

(3) Setting from GX Developer

The following parameters should be set through GX Developer in order to use

the Q series C24 mounted to a MELECNET/H remote I/O station.

Each of setting is the same way as when setting the parameters for the Q series

C24 mounted to a QCPU station: see Section 4.5 and after.

See the operating manual for GX Developer for how to display each setting

screen.

(Parameter setting items for the Q series C24 mounted to a MELECNET/H

remote I/O station)

Parameter setting item

Setting

Remarks

I/O Assignment

Set the module mounting information

See Section 4.5.1

Switch setting for I/O and

intelligent function module

Set the transmission specification and the

communication protocol for communication

with the external device

See Section 4.5.2

Remote password setting

Perform settings for the remote password.

User's Manual (Application)

Section 3.3.3

POINT

(1) Connect GX Developer to a MELECNET/H remote I/O station and set the

parameters.

(2) Reset the MELECNET/H remote I/O station after changing the setting.

(4) When monitoring/setting with GX Configurator-SC

(a) About the automatic refresh setting

1) When reading/writing data created by the automatic refresh setting

using PLC, the read/write operation should be performed by GX

Developer. It cannot be performed from GX Configurator-SC.

2) The devices used for the automatic refresh setting must be of the types

M, B, D, or W.

POINT

(1) GX Configurator-SC should be connected to a MELECNET/H remote I/O

station before the monitoring/setting.

(2) The MELECNET/H remote I/O station should be reset after changing the

setting.