Melsec-q, Point, 1) program conditions – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 328: 2) program examples

Advertising
background image

App. - 34 App. - 34

MELSEC-Q

APPENDIX

Appendix 9.2 When accessing buffer memory using sequence program

In the following program example, data are read from or written to the buffer memory of

the Q series C24 using the REMFR/REMTO instruction.

POINT

Use GX Configurator-SC to change the default value of the buffer memory. Using

GX Configurator-SC, save the new setting value to the flash ROM of the Q series

C24. (Refer to Chapter 8.)

(1) Program conditions

The following program reads data from or writes data to the QJ71C24N buffer

memory (CH1 side word/byte units designation area) when the read/write

command (X1020, X1021) turns ON.
(a) Devices used

:

• Read/write command.............................................................. X1020, X1021

• Read/write command pulse signal ......................................... M10, M11

• Completion device for REMFR/REMTO instruction .............. M100 to 103

• Normal/abnormal completion flag for REMFR/REMTO

instruction................................................................................ M200 to 203

• Read from word/byte units designation area ......................... D0

• Write to word/byte units designation area.............................. D1

(2) Program examples

(a) Read from buffer memory

<Read command>

Changes the read command
into pulses.

Abnormal completion of
REMFR instruction

Normal completion of
REMFR instruction

Reads the word/byte units
designation area data of the
buffer memory to D0.

(b) Write to buffer memory

<Write command>

<Write command>

Abnormal completion of
REMTO instruction

Changes the write command
into pulses.

Sets the word/byte units
designation to byte.

Transfers the setting value to
the word/byte units designation
area of the buffer memory.

Normal completion of
REMTO instruction

Advertising