Melsec-q – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 283

Advertising
background image

10 - 32 10 - 32

MELSEC-Q

10 TROUBLESHOOTING

10.3.4 Troubleshooting when an external device transmitted a message and "RD" LED

blinked, but the Read Request signal was not turned ON

Symptom

Cause

Corrective action

MC

Bidi

rectio

na

No

n

procedure

• Communication protocol

is set incorrect.

•

Check if the communication protocol is set correctly.

•

Check if the mode was switched without using the

buffer memory mode switching area.

Note

•

The communication protocol setting contents and

the communication protocol in the current operation

can be checked at buffer memory addresses 250

H

to (CH1) and 260

H

(CH2).

• When "Check CD

terminal" was set, the CD

terminal was turned off.

•

Since messages are skipped when the CD terminal is

turned OFF when "Check CD terminal" is set, change
the wiring so that the CD terminal remains on all the
time.

• When DC control is

selected, the necessary

DC codes are not

transmitted.

• Check if a message is transmitted without transmitting

"DC1 (11

H

)" after the external device transmits "DC3

(13

H

)" during DC1/DC3 external control.

• Check if the next message is transmitted without

adding "DC2 (12

H

)" after the external device transmits

"DC4 (14

H

)" during DC2/DC4 external control.

• The end code was not

received, or fixed length

data was not received.

•

Check if the end code set at the Q series C24 and the

end code transmitted from the external device are the
same.

•

Check if the external device transmitted the fixed

length designated at the Q series C24.

•

Check if the trailer frame was transmitted during

communications by user frame.

Note

•

When the send data from the external device is

correct, take the corrective action described in
Sections 10.3.10 and 10.3.11.

• The Q series C24

setting and message

format do not match.

• The data count basics, message format, etc. depend

on the following settings.

⋅

ASCII-BIN conversion enable/disable

⋅

Transparent code setting

⋅

User frame setting

See the relevant section for a description of operation
according to the set contents and setting of each item.

• An external device

transmitted a message

and "RD" blinked, but

the read request signal

(X0) was not turned

ON.

• The Q series C24 data

communications

monitoring time is set to

"infinite", or the

monitoring time is too

long.

•

Set, or shorten, the monitoring time and retransmit the

message from the external device and determine the
trouble from the contents of the time-out error.

Note

•

Error detection by the watchdog timer (timer 0 to

timer 2) is possible in the following cases.

⋅

When part of a message is skipped.

⋅

When transmission from an external device is

interrupted.

See Chapter 6 of User's Manual (Application) for a
detailed description of the monitoring time.