3 specifications, 1 performance specifications, Melsec-q – MITSUBISHI ELECTRIC QJ71C24N User Manual

Page 51: 33 specifications, 1) transmission specification

Advertising
background image

3 - 1 3 - 1

MELSEC-Q

3 SPECIFICATIONS

3

3 SPECIFICATIONS

The following shows the Q series C24 performance specifications.

See the User's Manual of the QCPU (Q mode) for general specifications.

3.1 Performance Specifications

The following shows the Q series C24 performance specifications. For the

transmission specifications when communicating via the modem function, see this

section and Chapter 3 of User's Manual (Application).

(1) Transmission specification

Specifications

Item

QJ71C24N

QJ71C24

QJ71C24N-R2

QJ71C24-R2

QJ71C24N-R4

CH1

RS-232-compliance

(D-sub 9 pin)

RS-232-compliance

(D-sub 9 pin)

RS-422/485-compliance

(2-piece plug-in connector socket

block)

Interface

CH2

RS-422/485-compliance

(2-piece terminal block)

RS-232-compliance

(D-sub 9 pin)

RS-422/485-compliance

(2-piece plug-in connector socket

block)

Line

Full-duplex/half-duplex communications

MC protocols

communication

Half-duplex communications

Non procedure protocol

communication

Full-duplex/full-duplex communications

Communications

system (

1)

Bidirectional protocol

communication

Full-duplex/full-duplex communications

Synchronization method

Start-stop synchronization method

[QJ71C24N(-R2/R4)]

50

300

600

1200

2400

4800

9600

14400

19200

28800

38400

57600

115200

230400

(bps)

•

Transmission speed 230400 bps is available for only CH1. (Not available for CH2)

•

Total transmission speed of two interfaces is available up to 230400 bps.

•

Total transmission speed of two interfaces is available up to 115200 bps when the communication data

monitoring function is used.

[QJ71C24(-R2)]

50

300

600

1200

2400

4800

9600

14400

19200

28800

38400

57600

115200

-

(bps)

Transmission speed

•

Total transmission speed of two interfaces is available up to 115200 bps.

Start bits

1

Data bits

7/8

Parity bits

1 (vertical parity) or none

Data format

Stop bits

1/2

MC protocol communication

Processes one request during installed PLC CPU END processing.

Number of scans that must be processed/number of link scans depends on the contents of the request.

(See Reference Manual.)

Access cycle

Non procedure protocol

communication

Bidirectional protocol

communication

Sends each time a send request is issued. Can receive at any time.

Parity check

All protocols and when ODD/EVEN is selected by parameter.

Error detection

Sum check code

MC protocol/bidirectional protocol selected by parameter.

Non procedure protocol selected by user frame.

(Continued on next page)