Description

Item

Inner Loop Error—Inner Loop Command summed with the Conditioner
Out signal.

Spool Position—Conditioner Out signal summed with the Spool Zero
signal.

Conditioner Out—Conditioned feedback signal from the servovalve’s
inner loop displacement sensor.

Spool Zero—Amount of offset introduced by the Conditioner tab’s
Offset control.

Ground—Signal common.

Inner Loop Tab Settings for Three-Stage Valve Drivers

Use this tab to define the inner loop tuning values.

Access

Station Setup window > navigation pane > Channels > Control Channel n >

> Inner Loop tab

Note:

To edit any item requires Tuning access level (or higher.)

Inner Loop Tab for Three-Stage Valve Drivers

Description

Item

Sets the inner loop’s proportional gain, which affects the inner loop
response of the pilot valve.

Inner Loop Gain

Sets the inner loop’s derivative gain, which affects the servovalve’s
stability at higher inner loop gain settings.

Inner Loop Rate

Spool Position—Sets the feedback from the servovalve’s spool as
the rate input. Most systems use this setting.

Rate Input Selection

Inner Loop Error—Sets the inner loop error as the rate input. This is
the difference between spool position feedback and spool position
command.

Conditioner Tab Settings for Three-Stage Valve Drivers

Use this tab to define the inner loop conditioner values.

Access

Station Setup window > navigation pane > Channels > Control Channel n >

> Conditioner tab

228 MTS Series 793 Control Software

Station Setup