Rockwell Automation 5730 DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control User Manual

Page 107

Advertising
background image

Communicating with Devices on an EtherNet/IP Link

6-3

Assigning Network Parameters with BOOTP/DHCP

The EtherNet/IP Option board ships with BOOTP enabled. You must assign
an IP address to the Ethernet port in order for the controller to communicate
over an EtherNet/IP network.

The BOOTP/DHCP utility is a stand alone program that is located in the:

• BOOTP-DHCP Server folder in the Rockwell Software program folder

on the Start menu (the utility is automatically installed when you install
RSLinx software)

• Tools directory on the RSLogix 5000 installation CD.

The computer running the BOOTP/DHCP utility and the DriveLogix5730
controller must be on the same EtherNet/IP network.

To use the BOOTP/DHCP utility:

ahw0861.ti

f

1.

Start the BOOTP/DHCP software.

2.

From the Tools menu, select Network Settings.

ahw0858.ti

f

Click OK.

3.

Enter the required data.

Note: If you have not run the BOOTP/DHCP program before,
it will automatically launch the Network Settings window.