What is DriveLogix5730?

1-11

The interruption of a periodic task increases the elapsed time (clock time)
between the execution of system overhead, as shown below.

If you increase the time slice to 20%, the system overhead interrupts the
continuous task every 4 ms (of continuous task time).

If you increase the time slice to 50%, the system overhead interrupts the
continuous task every 1 ms (of continuous task time).

If the controller only contains a periodic task(s), the system overhead
timeslice value has no effect. System overhead runs whenever a periodic
task is not running.

1 ms

1 ms

1 ms

1 ms

1ms

periodic task

1 ms

1 ms

system overhead

9 ms of continuous task time

9 ms of continuous task time

continuous task

0

5

10

15

20

25

elapsed time (ms)

1 ms

1 ms

1 ms

1 ms

1 ms

system overhead

4 ms

4 ms

4 ms

4 ms

4 ms

continuous task

5

10

15

20

25

elapsed time (ms)

1 ms

system overhead

1 ms

continuous task

5

10

15

20

25

elapsed time (ms)

periodic task

system overhead

5

10

15

20

25

continuous task

elapsed time (ms)