Chapter 4, Configuring drivelogix motion, About this chapter – Rockwell Automation 5730 DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control User Manual

Page 71: System requirements

Advertising
background image

Chapter

4

Configuring DriveLogix Motion

De-energizing the Drive to
Connect or Disconnect a
Cable

During the process of configuring DriveLogix motion you will need to
connect or disconnect a programming or network cable at the controller.
You should do this only if the drive is de-energized.

1. Turn off and lock out input power. Wait five minutes.

2. Verify that there is no voltage at the drive’s input power terminals.

3. Measure the DC bus voltage at the +DC & -DC terminals on the Power

Terminal Block. The voltage must be zero.

4. Connect or disconnect the programming or network cable.

5. Turn power back on and proceed with configuring DriveLogix motion.

About this Chapter

This chapter introduces DriveLogix5730 motion. The steps in this chapter
provide the minimum settings required to begin testing DriveLogix motion.

System Requirements

• PowerFlex 700S Phase II Drive with firmware revision 2.XX or higher

• DriveLogix5730 Controller with firmware revision 15.XX or higher

• DriveExecutive programming software version 3.02 or higher

• RSLogix 5000 programming software version 15 or higher

!

ATTENTION: Severe injury or death can result from electrical
shock or burn. Verify that the voltage on the bus capacitors has
discharged before connecting to the communication ports.
Measure the DC bus voltage at the +DC & -DC terminals on the
Power Terminal Block. The voltage must be zero.

Advertising
This manual is related to the following products: