Communicating with Devices on a ControlNet Link

7-19

Example 1: Total Connections Required by DriveLogix1

The following table calculates the connections used in this example.

If you configured the remote I/O modules as rack-optimized, you would
only need a rack-optimized connection to the 1794-ACNR15, reducing the
above example by 3 connections.

Example 2: DriveLogix5730
Controller to
DriveLogix5730 Controller

In the following example, one DriveLogix5730 controller communicates
with another DriveLogix5730 controller over ControlNet. Each DriveLogix
controller has its own local I/O.

Example 2: Sending a MSG Instruction

To send a MSG from DriveLogix1 to DriveLogix2:

1. For DriveLogix1, create a controller-scoped tag and select the

MESSAGE data type.

2. Enter a MSG instruction.

In this example logic, a message is sent when a specific condition is met.
When count_send is set, the ladder logic sends the count_msg MSG.

Connection:

Amount:

DriveLogix1 controller to 3 local I/O modules
rack-optimized connection for the DIN rail
direct connection for each I/O module

1
3

DriveLogix1 controller to remote 1794-ACNR15

1

DriveLogix1 to 4 remote I/O modules (through 1794-ACNR15)
all I/O modules configured as direct connection
no connection to the 1794-ACNR15

4

total connections used: 9

ahw0934.eps

DriveLogix5730 Controller
(DriveLogix1)

ControlNet

DriveLogix5730 Controller
(DriveLogix2)

workstation

ahw0913

.eps