6-28

Communicating with Devices on an EtherNet/IP Link

Configuring the MSG Instruction that Transmits the Email

a

hw0900.tif

1.

On the Configuration tab of the Message Configuration, fill out the following fields:

In this field:

Enter:

Service Type

Custom

Service Code

4b

Instance

1

Class

32f

Attribute

0

Source Element

the tag that contains the email text
This tag is of the STRING data type you created to contain the email text. In this
example, EmailText.

Source Length

the number of characters in the email text plus 4
In this example, enter 114 (110 characters in the email + 4)

Destination

a tag to contain the status of the email transmission
This tag is also of the STRING data type you created to contain the email text. In
this example, EmailStatus.