Rockwell Automation 5730 DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control User Manual

Page 15

Advertising
background image

What is DriveLogix5730?

1-3

The controller’s EtherNet/IP configuration settings are maintained during a
flash process.

If you load firmware via an EtherNet/IP connection, browse through the
network port, across the virtual backplane, and select the appropriate
controller.

Using ControlFlash to load firmware

You can use ControlFlash to load firmware through either an Ethernet
connection (an IP address must already be assigned to the Ethernet port) or
a serial connection.

1. Make sure the appropriate network connection is made before starting.

2. Start the ControlFlash utility. Click Next when the Welcome screen

appears.

3. Select the catalog number of the controller and click Next.

4. Expand the network until you see the controller. If the required network

is not shown, first configure a driver for the network in RSLinx software.

If you use an Ethernet connection to load the firmware (which is much
faster than the serial connection), the utility will require a valid IP
address before connecting to the controller.

5. Select the controller and click OK.

6. Select the revision level to which you want to update the controller and

click Next.

7. To start the update of the controller, click Finish and then click Yes.

8. After the controller is updated, the status box displays Update complete.

Click OK.

9. To close ControlFlash software, click Cancel and then click Yes.