7-2

Communicating with Devices on a ControlNet Link

sure it’s properly installed in the DriveLogix controller. Refer to

Installing

the Communications Daughtercard on page B-9

.

You’ll need to configure the communication daughtercard slot number to 1
in the RSLogix 5000 programming software. The DriveLogix controller
uses slot 0 for the Communication Format with the local drive.

For more information about configuring a 1788-CNx communication
daughtercard, see:

Configuring the Communication Driver

Use RSLinx software to configure the ControlNet communication driver.
Select the appropriate communication driver for the communication
daughtercard in your workstation.

For this card:

See this document:

1788-CNC, -CNCR

1788-IN002

1788-CNF, -CNFR

1788-IN005

1.

In RSLinx software, select Configure Driver. Select the appropriate driver.

The installation instructions for the communications daughtercard should identify
which communication driver to install.

ahw04

33.tif

ahw0434.ti

f

2.

Specify the appropriate settings. For example.

If you are using this device:

Specify this information:

1784-KTCx card

memory address, which must match the switch setting on the card
I/O base address, which must match the switch setting on the card
ControlNet node address

1784-PCC card

ControlNet node address (MAC ID)

1784-PCIC card

ControlNet node address (MAC ID)