7-26

Communicating with Devices on a ControlNet Link

Example 3: Total Connections Required by DriveLogix1

The following table calculates the connections used in this example.

If you configured the local I/O modules as rack-optimized, you would only
need the DIN-rail connection to the I/O modules, reducing the above
example by 3 connections.

You can configure the 1756-CNB module to use no connection. This is
useful if you configure all direct connections to their associated I/O
modules and do not need a rack-optimized connection.

Connection:

Amount:

DriveLogix1 controller to 3 local I/O modules
rack-optimized connection for the DIN rail
direct connection for each I/O module

1
3

DriveLogix1 controller to local 1788-CNC

0

DriveLogix1 controller to remote 1756-CNB

1

DriveLogix1 controller to remote ControlNet PLC-5

1

connected, cached MSG from DriveLogix1 to Control1

1

connected, cached MSG from DriveLogix1 to PLC5C1

1

Produced TagA
produced from DriveLogix1 to DriveLogix2
consumed by PLC5C1

1
1

Consumed TagB from DriveLogix2

1

Consumed INT from PLC5C1

1

total connections used: 12