Communicating with Devices on a DH485 Link

9-7

Connections Using Belden 3106 Cable

The table and schematic diagram below shows wire/terminal connections
for Belden 3106A cable.

Connections Using Belden 9842 Cable

The table and schematic diagram below shows wire/terminal connections
for Belden 9842 cable.

For this Wire/Pair

Connect this Wire

To this Terminal

white/orange

orange with white stripe

5 - Data A)

white with orange stripe

4 - (Data B)

blue

blue

3 - (Common)

shield/drain

non-jacketed

2 - Shield

For this Wire/Pair

Connect this Wire

To this Terminal

white/orange

orange with white stripe

5 - (Data A)

white with orange stripe

4 - (Data B)

blue/white

white with blue stripe

cut back - no connection

(1)

(1)

To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the insulation jacket is removed. This wire is not used by DH-485.

blue with white stripe

3 - (Common)

shield/drain

non-jacketed

2 - Shield

Termination

Data A

Data B

Common

Shield

Chassis Ground

WH/OR

OR/WH

BU

6

5

4

3

2

1

ahw0604.eps

Termination

Data A

Data B

Common

Shield

Chassis Ground

WH/OR

OR/WH

6

5

4

3

2

1

WH/BU

BU/WH

ahw0609.eps