Rockwell Automation 5730 DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control User Manual

Page 95

Advertising
background image

Communicating with Devices on a Serial Link

5-3

Configuring the Serial Port of the Controller

Characteristic:

Description (default is shown in bold):

Mode

Select System (for DF1 communication) or User mode (for ASCII communication).

Baud rate

Specifies the communication rate for the serial port. Select a baud rate that all devices in your
system support.
Select 110, 300 600, 1200, 2400, 4800, 9600, 19200, or 38400 Kbps.

Parity

Specifies the parity setting for the serial port. Parity provides additional message-packet error
detection.
Select None or Even.

Data bits

Specifies the number of bits per message packet.
Select 8.

Stop bits

Specifies the number of stop bits to the device with which the controller is communicating.
Select 1 or 2.

Control line

Specifies the mode in which the serial driver operates.
Select No Handshake, Full-Duplex, Half-Duplex with Continuous Carrier, or Half-Duplex without
Continuous Carrier.
If you are not using a modem, select No Handshake
If both modems in a point-to-point link are full-duplex, select Full-Duplex for both controllers.

1.

In the Controller Organizer, select the Controller folder. Right-click the
selected folder and select Properties.

2.

On the Serial tab, specify serial port characteristics.

a

hw0916.tif

ah

w0915.tif