Placing and Configuring the Drive

2-17

Configuring the Drive’s Response to a Connection Failure or Controller
Mode Change

The drive contains several parameters that allow you to configure the drive’s
response to communication loss to the controller. From the drive’s
perspective, a communication loss can come in the following two forms.

• The controller closes the connection (for example, the connection is

inhibited).

• A general failure occurs causing the connection to time out.

Parameter 386 [Lgx OutofRunCnfg] configures the drive’s response to the
controller is removed from the Run Mode. Parameter 387 [Lgx Timeout

2.

To send additional data from the drive to the controller, go to the To DriveLogix tab.

Click the button in front of the

UserDefinedRealData[0] tag

ahw079

0.tif

ah

w

0

791.tif

3.

Select the desired source (parameter 307 [Output Voltage] in this example) in the resulting window.