Placing and Configuring Local I/O

3-11

inhibit or 0 to uninhibit). Use a SSV instruction to write the Mode attribute
back to the module. For example:

Sending Module Configuration Information

The controller sends module configuration information once module
connections are established.

The GSV instruction gets the current status of the module named “input_module.” The SSV instruction sets the state of “input_module” as either
inhibited or uninhibited.

When on, inhibits the module.
When off, uninhibits the module.

GSV l

adder

.ti

f

!

ATTENTION: If you make a configuration change to any
module in the system do one of the following to resend module
configuration data:

• cycle power to the controller

• inhibit and then uninhibit the bus

• inhibit and then uninhibit the individual module

• send a MSG instruction of type Module Reconfigure (for

information on configuring a MSG to send configuration data,
see the Logix5000 Controllers General Instructions Reference
Manual, publication 1756-RM003)