Placing and Configuring Local I/O

3-19

Entering the Configuration Information for the Module

Once you configure a module using the generic 1769-MODULE, you must
enter the configuration information for the module into the tag database.
The configuration information is downloaded to the module at program
download, power up, and whenever a module is inhibited and then
uninhibited.

RSLogix 5000 programming software automatically create tags for
configured I/O modules. All local I/O addresses are preceded by the word
Local. These addresses have the following format:

• Input Data: Local:s:I

• Output Data: Local:s:O

• Configuration Data: Local:s:C

Where s is the slot number assigned the I/O module.

Open the configuration tag for that module by clicking on the plus sign to
the left of its configuration tag in the tag database. The configuration
information depends on the module. See the documentation on the I/O
module for the appropriate configuration information.

2.

Edit the tags for the module so that the tags contain the appropriate configuration

ah

w

0

822.tif

ahw0823.tif

1.

In the Controller Organizer, double-click on Controller Tags.

The generic module was added to slot 3, so you want to enter
configuration data into the Local:3:C tags.