7-18

Communicating with Devices on a ControlNet Link

Determining the API

The API (actual packets per interval) is related to the RPI for the connection
and the NUT of the network. Use this table to select the API to enter in the
above worksheet:

Example 1: DriveLogix
Controller and Remote I/O

In the following example, one DriveLogix5730 controller controls remote
I/O through a 1794-ACN15 module.

Example 1: Controlling Remote Devices

This example has DriveLogix1 controlling the I/O connected to the remote
1794-ACN15 module. The data the DriveLogix controller receives from the
remote I/O modules depends on how you configure the remote I/O modules.
You can configure each module as a direct connection or as rack optimized.
One chassis can have a combination of some modules configured as a direct
connection and others as rack optimized.

If:

Enter this value for the API:

RPI

≥ NUT and RPI < 2∗NUT

NUT

RPI

≥ 2∗NUT and RPI < 4∗NUT

2

∗NUT

RPI

≥ 4∗NUT and RPI < 8∗NUT

4

∗NUT

RPI

≥ 8∗NUT and RPI < 16∗NUT

8

∗NUT

RPI

≥ 16∗NUT and RPI < 32∗NUT

16

∗NUT

RPI

≥ 32∗NUT and RPI < 64∗NUT

32

∗NUT

RPI

≥ 64∗NUT and RPI < 128∗NUT

64

∗NUT

RPI

≥ 128∗NUT

128

∗NUT

ahw0933.eps

DriveLogix5730 Controller
(DriveLogix1)

1794-ACN with remote I/O
(Remote1)

ControlNet