Rockwell Automation 5730 DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control User Manual

Page 124

Advertising
background image

6-20

Communicating with Devices on an EtherNet/IP Link

Communicating with Another Logix-based Controller

All Logix-based controllers can use MSG instructions to communicate with
each other. The following examples show how to use tags in MSG
instructions between Logix-based controllers.

The source and destination tags:

• must be controller-scoped tags.

• can be of any data type, except for AXIS, MESSAGE, or

MOTION_GROUP.

Communicating with other controllers over EtherNet/IP

The DriveLogix5730 controller also uses MSG instructions to communicate
with PLC and SLC controllers. The MSG instructions differ depending on
which controller initiates the instruction.

For MSG instructions originating from a DriveLogix5730 controller to a
PLC or SLC controller:

Type of MSG Instruction:

Example Source and Destination:

Logix-based controller writes to Logix-based
controller
(CIP Data Table Write)

source tag

destination tag

array_1

array_2

Logix-based controller reads from
Logix-based controller
(CIP Data Table Read)

source tag

destination tag

array_1

array_2

Type of MSG
Instruction:

Supported Source File Types:

Supported Destination File Types:

DriveLogix5730
writes to PLC-5 or
SLC

In the DriveLogix5730 controller, specify the source data type
based on the destination device:

PLC-5: SINT, INT, DINT, or REAL
SLC: INT, REAL

Example source element: array_1

Specify the destination file type based on the
destination device:

PLC-5 typed write: S, B, N, or F
PLC-5 word-range write: S, B, N, F, I, O, A, or D
SLC: B, N or F

Example destination tag: N7:10

Advertising
This manual is related to the following products: