2-18

Placing and Configuring the Drive

Cnfg] configures the drive’s response to a general connection failure as
detected by the drive. Parameter 388 [Lgx Closed Cnfg] configures the
drive’s response to the controller closing the connection. All of these
parameters configure the drive’s response to these exception events in the
following ways: ignore, alarm, fault and coast to stop, fault and ramp to
stop, fault and stop in current limit.

Parameter 385 [Lgx CommLossData] determines what the drive does with
data from the controller when communication is lost. It determines if the
drive resets the data to zero or holds the data in its last state.

Configure these parameters, using DriveExecutive Lite. Locate them in the
Fault/Alm Config group of the Utility file.