DriveLogix5730 Controller Specifications

A-7

Network Status (NS) indicator

Link Status (LNK) indicator

solid red

held in reset

The controller is holding the port in reset or the
controller is faulted.

Clear the controller fault.
Replace the controller.

self-test

The port is performing its power-up self-test.

Normal operation during power-up. No action
required.

major fault

An unrecoverable fault has occurred.

Cycle power to the controller.
Replace the controller.

flashing red

updating firmware

The port firmware is being updated.

Normal operation during firmware update. No
action required.

Condition:

Status:

Indicates:

Recommended Action:

Condition:

Status:

Indicates:

Recommended Action:

off

not initialized

The port does not have an IP address and is
operating in BOOTP mode.

Verify that the BOOTP server is running.

flashing green

no CIP
connections
established

The port has an IP address, but no CIP connections
are established.

Normal operation if no connections are
configured. No action required.
If connections are configured, check connection
originator for connection error code.

solid green

CIP connections
established

The port has an IP address and CIP connections
(Class 1 or Class 3) are established.

Normal operation. No action required.

solid red

duplicate IP
address

The port has detected that the assigned IP address is
already in use.

Verify that all IP addresses are unique.

flashing red/green

self-test

The port is performing its power-up self-test.

Normal operation during powerup.

Condition:

Status:

Indicates:

Recommended Action:

off

no link

The port is not connected to a powered Ethernet
device.
The port cannot communicate on Ethernet.

Verify that all Ethernet cables are connected.
Verify that Ethernet switch is powered.

flashing green

self-test

The port is performing its power-up self-test.

Normal operation during powerup.

data transmission
and reception

The port is communicating on Ethernet.

Normal operation.
No action required.

solid green

link OK

The port is connected to a powered Ethernet device.
The port can communicate on Ethernet.

Normal operation.
No action required.