Example 3: drivelogix controller to other devices – Rockwell Automation 5730 DriveLogix5730 Controller for PowerFlex 700S Drives with Phase II Control User Manual

Page 162

Advertising
background image

7-22

Communicating with Devices on a ControlNet Link

Each produced tags requires one connection for the producing controller
and an additional connection for each consuming controller. Each
consumed tag requires one connection.

Example 2: Total connections required by DriveLogix1

The following table calculates the connections used in this example.

If you configured the local I/O modules as rack-optimized, you would only
need the DIN-rail connection to the I/O modules, reducing the above
example by 3 connections.

Example 3: DriveLogix
Controller to Other Devices

In the following example, one DriveLogix controller communicates with a
Logix5550 controller and a ControlNet PLC-5 controller over ControlNet.

Connection:

Amount:

DriveLogix1 controller to 3 local I/O modules
rack-optimized connection for the DIN rail
direct connection for each I/O module

1
3

DriveLogix1 controller to local 1788-CNC

0

DriveLogix1 controller to remote 1788-CNC

0

connected, cached MSG from DriveLogix1 to DriveLogix2

1

produced tagA
produced from DriveLogix1 to DriveLogix2
other consumer (2 are configured)

1
1

produced tagA
produced from DriveLogix1 to DriveLogix2
other consumer (2 are configured)

1
1

consumed TagB

1

total connections used: 10

ahw0936

.eps

DriveLogix5730 Controller
(DriveLogix2)

ControlNet

DriveLogix5730 Controller
(DriveLogix1)

ControlLogix Controller
(Control1)

ControlNet PLC5
Controller
(PLC5C1)