Operator Interface 3-35

7000 “B” Frame

7000-UM150I-EN-P – June 2013



Figure 3.43 – Modify Numerical Value

To be allowed to make changes to the parameter, the operator
interface must be set to an Access Level other than 'Monitor'. (You
will be able to view the screen; however, pressing the data entry keys
will have no effect). If you are not in the correct level, press the [F8]
key in order to gain access to the parameter. Refer to the section
entitled Enter/Modify an Access Level for further information on
the operation to change the level.


Having gained access, use the data entry keys [0]-[9] to enter the
new value. The [-] key can be typed at any time to enter a negative
value. The [.] key is used to enter a decimal point for fractional
values. The entered new value can be edited by pressing the
[backspace] key. This key will delete the right most character (i.e.
number, decimal point or negative sign) shown on the screen. Press
the [enter] key to accept the new value as shown in Figure 3.43. If
the new value that you entered is outside the limits defined, the new
value will not change. For example: If you entered 900 when the
minimum value was 4000, the new value will still show 4100.


Some data must be entered in HEX. To accomplish this, use the
cursor up/down keys to scroll through the values 0-F for the right
most digit. To accept the digit and enter to the right of the current
digit, press the right cursor key. Press the [Enter] key to accept the
value.


The value may be edited the same as a value entered from the
numeric keypad.


The new value is not sent to the drive until you exit the screen with
the [F10] key. Prior to this you can modify the new value by
repeating the above procedure, or you can cancel the change by
pressing the [F7] key. The CANCEL operation returns the new
value to that of the actual value.