Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 442

Advertising
background image

7-20

Troubleshooting

7000-UM150I-EN-P – June 2013

7000 “B” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Rect HeatSink OT

193

The temperature detection on the Rectifier
Heatsink, connected to Channel A fiber optic
receiver RX7 on FOI-L-A, has exceeded

Rectifier Heatsink Temperature Trip (P315).

– Confirm actual temperature in

parameters is not higher than the trip
value – If so, investigate the conditions of

the drive (ambient/ loading/ elevation /
ventilation/ filter status /heatsink
clogging)

– Check TFB and FOI board for power and

fiber optic integrity

– Check the sensor and temperature

offline (ambient) for accuracy

Rect ChannelB OT

194

Not Normally Used - The temperature
detection on a Rectifier Heatsink, connected

to fiber optic receiver RX7 on FOI-L-B, has
exceeded Rectifier Temperature Trip

Channel B (P525).

Rec HS Sensor

201

The drive has detected a missing
temperature sensor connected to the TFB
on the rectifier heatsink. A missing sensor
can result in either a Fiber Optic Loss fault
or a Sensor fault because a missing sensor
can be interpreted as either 0°C or over

100°C, and both are unrealistic values.

– Verify sensor is completely seated

properly on TFB.

– Measure sensor resistance.
– Replace if necessary.

Rec ChB Sensor

202

Not normally used: The drive has detected
a missing temperature sensor connected to
the optional TFB connected to the fiber optic

receiver RX7 on FOI-L-B. A missing sensor
can result in either a Fiber Optic Loss fault
or a Sensor fault because a missing sensor

can be interpreted as either 0°C or over
100°C, and both are unrealistic values.

RNeutral OL

203

The neutral resistor required for Direct-to-
Drive technology has reached an overload
condition. This is determined from

parameters R Neutral (P680), R Neutral
Rating (P681). The current through the

neutral resistor is calculated by measuring
the voltage across the resistor and knowing
the resistance. I Common Mode (P697)

displays that current, and R Neutral OL
(P682) shows the overload accumulator.
The resistor is allowed 500% for 10 seconds

every 5 minutes, and P682 is normalized to
fault whenever the value reaches 1.00.

– Verify the resistor ratings
– Verify that the drive Voltage Feedback

Splitter board is operating properly

– Investigate the possibility of voltage

unbalances on the input or output of the

drive that would create a voltage
differential across the resistor

– Contact the factory for further

instructions

SCB Incompat

177

Signal Conditioning Board Incompatible

– This is for DTD drive only
– The SCB -280 and 380 are used in DTD

drive. The boards have different filter that
cause this fault.

– Use -380 board on SCBL and SCBM

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Advertising