Component Definition and Maintenance 6-103

7000 “B” Frame

7000-UM150I-EN-P – June 2013

-

Under Protocol, click the arrow on the right to open
the dropdown list. Select Xmodem from the list and
then click on Send button. This will start the
download process, and a window similar to the one
shown below will appear showing download
progress.

-

After the download is complete, the “Download
Successful
” message will appear inside the
HyperTerminal window. At this point the system is
still in download mode. Now, close the
HyperTerminal program and disconnect your laptop
from the drive and cycle the control power to drive
control boards.


-

After the boards are powered up, you need to
transfer the parameters from the Terminal memory
back to drive. Refer to “Reloading the Parameters
described below.

NOTE: While the system is powered down, the system should be
inspected for a DIM module. This is an external memory module
mounted on the CIB, in P50-40. If this module is installed and at an
earlier major database revision than the new firmware installed, it
should be removed. The drive will give you an INVALID DIM fault
when you re-power the drive with the module still installed.

Reloading the Parameters

Once power is reapplied, the drive may come up will all the
parameters from NVRAM. But if you have upgraded the firmware
from one main revision level to another (i.e. 2.002 to 3.001), the
NVRAM will be cleared. All other information such as operating
hours, external fault messages, specific drive name, trending setup,
etc. are also cleared. If you have upgraded the firmware from one
minor revision level to another (i.e. 3.002 to 3.004), the NVRAM
will still be intact.