Control power tests, Three phase input – Rockwell Automation 7000 PowerFlex Medium Voltage AC Drive (B Frame) - Classic Control User Manual

Page 199

Advertising
background image

4-40

Commissioning

7000-UM150I-EN-P – June 2013

7000 “B” Frame

Control Power Tests

Prior to energizing the drive, verify that the control power being
fed into the input breakers are rated as designated on the
electrical diagram.


Although there are a variety of options available to customers
that will effect the control power distribution within the drive,
the input will always be as illustrated below:


+24V - PRINT,I/O

Fan

DC/DC

CONVERTER

DC/DC

WARN

SPGDB P/S

FAIL

+5V - LOGIC

+/-15V - LOGIC

+/-24V - LEM

+12V - REM I/O

+15V - TACH

C

hold-up

DC/DC

FAIL

3phase

20V

ISOLATED

GATE DRIVER

POWER SUPPLY

6

20V

PV550 &

Remote I/O

Single

phase

DC

FAIL

AC

FAIL

3 phase

AC/DC

converter

56V

1500W

4

Grounded
neutral

208 V

120 V

CB1

(Optional

CPT)

Figure 4.13 – Control Power Distribution


Three Phase Input


In the 3 phase input configuration, the customer supplies 3 phase
control power into the Fan Disconnect Switch (Labeled FDS1 on the
Electrical Schematics). From that point, the power is distributed to
all the power supplies and controls within the drive. The 3-phase
control should be measured at the input to FDS1. If the rating
matches the designation on the electrical schematic, it is acceptable
to apply control power to the drive. Take necessary measures to
rectify the control power level in the event that it does not meet the
design specifications.